PART XXVI ELECTRICAL OPERATIONS — Low voltage electrical equipment - disconnection and lockout
484
(1) Low voltage electrical equipment shall be completely disconnected and locked out where required by Part IX before work is started on it.
484(2)
Where it is not practicable to completely disconnect low voltage electrical equipment, work shall be performed in accordance with an electrical safety program in accordance with a standard acceptable to the minister that
484(a)
includes emergency procedures and emergency release of victims;
484(b)
requires the use of appropriate electrical protective equipment, including flame retardant clothing, voltage-related rubber gloves and cover up and other necessary live line tools;
484(c)
provides that, where practicable, uncontrolled liquid is not permitted close to a worker working on the equipment;
484(d)
prohibits the use of metal ladders, wooden ladders with wire reinforced side rails, metal scaffolds or metal work platforms; and
484(e)
has available up to date diagrams.