PART XXVI ELECTRICAL OPERATIONS — Working close to low voltage energized equipment
486
(1) Uninsulated, energized parts of low voltage electrical equipment shall be guarded by approved cabinets or enclosures unless the energized parts are in a suitable room or similar enclosed area that is accessible only by qualified persons.
486(2)
An entrance to a room or other guarded location containing uninsulated and exposed energized parts shall be marked with a conspicuous warning sign limiting entry.
486(3)
Where uninsulated energized parts are not guarded with approved cabinets or enclosures
486(a)
a suitable barrier or cover shall be provided where a worker unfamiliar with the hazards is working within the limited approach boundary of 1.07 metres of the uninsulated, energized parts; or
486(b)
a worker shall be informed of the potential hazards and provided with and follow appropriate written safe work procedures.