PART XXVI ELECTRICAL OPERATIONS — Grounding and blocking
496
(1) While a safety protection guarantee is in effect, the equipment to be worked on shall be tested to verify isolation before grounding and blocking begin.
496(2)
After the testing referred to in subsection (1) has been done, the person at the worksite responsible for a crew shall verify that the required grounding and blocking devices are in place before work begins.
496(3)
Grounding and blocking of equipment that may be hazardous to workers shall be carried out as closely as practicable to the worksite.
496(4)
Where grounding and blocking is not safe or practicable, written safe work procedures acceptable to the minister shall be followed.
496(5)
Grounding and blocking devices may be removed for the purpose of conducting tests after lockout procedures have been followed.