PART XXVI ELECTRICAL OPERATIONS — Assurance not practicable
500
(1) Where exposed high voltage electrical equipment and conductors cannot be isolated, rerouted or guarded, work shall not be done within the minimum distance specified under subsection 498 (3) until approval is obtained from the minister and the following precautions are taken:
500(a)
the area within which equipment or materials are to be used shall be barricaded and supervised to restrict entry only to those workers necessarily engaged in the work;
500(b)
a safety watcher shall be designated; and
500(c)
a positive means shall be provided for the safety watcher to give a clear, understandable stop signal to workers in the area, and watcher shall not give the stop signal by another means.
500(2)
While equipment is in motion in an area in proximity to energized electrical equipment or conductors, a person other than the equipment operator shall not touch a part of the equipment or the material being moved by it.
500(3)
A person shall not move a load or rigging line from its position of natural suspension where the load or rigging line is in proximity to an energized electrical conductor or equipment.