NL · Occupational Health and Safety Regulations (workplace standards) · Article 60 · clause 60 · NLR 5/12

PART VI OCCUPATIONAL HEALTH REQUIREMENTS — Dispensing

60

Where a flammable liquid is dispensed or transferred inside a flammable liquids storage room,

60(a)

the storage room shall be mechanically ventilated at a rate of at least 18 m3/hr a square metre of floor area (1 cfm/sq ft), but not less than 250 m3/hr (150 cfm);

60(b)

exhaust air shall be discharged to the outdoors, and makeup air provided;

60(c)

makeup air duct passing through a fire separation shall be equipped with an approved fire damper; and

60(d)

doors shall be self-closing.