NL · Occupational Health and Safety Regulations (workplace standards) · Article 683 · clause 683 · NLR 5/12

PART XXXIII USE OF ELECTRICITY IN MINES — Transformers

683

(1) Transformers shall be of a type and design suitable for the location in which they are to be installed.

683(2)

Where installed underground, a transformer shall

683(a)

be protected against physical damage;

683(b)

be guarded to prevent access by unauthorized persons;

683(c)

be in an electrical equipment vault;

683(d)

be separated from explosives storage areas by 15 metres of undisturbed rock or a distance of 60 metres; and

683(e)

have clearances around it to permit safe access for inspection, maintenance, and repairs.