PART XXXIII USE OF ELECTRICITY IN MINES — Protection of trailing cables
686
(1) Trailing cables shall be routed to avoid accumulation of water and damage and be kept visible by being mounted on suitable markers at regular intervals throughout the cable route.
686(2)
Cable couplers shall be suitably supported off the ground.
686(3)
Where trailing cables cross haulageways, or where equipment shall pass the cables, cables shall be isolated by elevation or be protected from crushing.
686(4)
A cable assembly operating at a voltage in excess of 300 volts shall be provided with a visible means of identifying the equipment to which it is connected or by other means acceptable to the minister.
686(5)
Trailing cables shall be kept under observation by the machine operator or assistant to effectively prevent damage to them.
686(6)
Where trailing cables receive mechanical or electrical damage they shall be removed from service immediately.
686(7)
A worker shall not drive a vehicle over an unprotected trailing cable.