NL · Occupational Health and Safety Regulations (workplace standards) · Article 689 · clause 689 · NLR 5/12

PART XXXIII USE OF ELECTRICITY IN MINES — Quick connect cable couplers

689(g)

a disconnecting device placed less than one metre from the receptacle.

689

(1) A quick connect coupler used to join portable cables or a cable and a flange mount receptacle, operating at a voltage in excess of 300 volts shall have

689(a)

a mechanical fastening arrangement, to join the coupler, with a tensile strength greater than that of the portable power cable;

689(b)

strain relief devices suitable for the intended portable power cable;

689(c)

a means to prevent the ingress of moisture;

689(d)

a means to mechanically lock the coupler, where the circuit voltage exceeds 750 volts;

689(e)

a pin arrangement that

689(i)

the ground conductor makes before and breaks after the phase conductors, and (ii) the ground check circuit makes after and breaks before the phase conductors;

689(f)

ground fault protection and ground conductor monitoring at the source of supply; and

689(2)

A disconnecting device shall be used to de-energize the receptacle before a plug is connected or disconnected.