PART XXIX UNDERGROUND OPERATIONS — Fire suppression system
573
An employer shall provide and maintain a fire suppression system consisting of sprinklers, foam or other suitable means of suppressing a fire
573(a)
on each piece of equipment containing more than 25 litres of flammable fluids;
573(b)
on each piece of equipment operated by remote control;
573(c)
at each underground fuel storage area or fueling area where more than 500 litres of oil, grease or combustible liquids are stored; and
573(d)
in a building or structure, except a fan house located above or adjacent to an opening to an underground mine.