STU
NL · Occupational Health and Safety Regulations (workplace standards) · Article 573 · clause 573 · NLR 5/12

PART XXIX UNDERGROUND OPERATIONS — Fire suppression system

573

An employer shall provide and maintain a fire suppression system consisting of sprinklers, foam or other suitable means of suppressing a fire

573(a)

on each piece of equipment containing more than 25 litres of flammable fluids;

573(b)

on each piece of equipment operated by remote control;

573(c)

at each underground fuel storage area or fueling area where more than 500 litres of oil, grease or combustible liquids are stored; and

573(d)

in a building or structure, except a fan house located above or adjacent to an opening to an underground mine.

Not legal advice. Verify the cited article against the signed agreement.